Amir Heidary, Hamid Radmanesh, Seyed Hamid Fathi, G. B. Gharehpetian. Series transformer based diode-bridge-type solid state fault current limiter[J]. Frontiers of Information Technology & Electronic Engineering,in press.https://doi.org/10.1631/FITEE.1400428 @article{title="Series transformer based diode-bridge-type solid state fault current limiter", %0 Journal Article TY - JOUR
Abstract: This paper solves some problems about the fault current: Firstly, it can limit the fault current effectively by two current limiting modes. Secondly, the series RC branch, connected in parallel with the IGBT, serves as a snubber circuit for decreasing the Transient Recovery Voltage (TRV) of the IGBT during on-off states. At last, the general control strategy can achieve the fault current to be tightly controlled and the inrush current problem is eliminated.
基于级联变压器的二极管桥式固态故障电流限制器创新点:所描述的SSFCL具有简单且易用的结构,能够将故障电流幅度限制于安全范围内。并能减少谐波畸变与开关电压过冲,调控公共耦合点电压。 方法:将一串联RLC支路连接于隔离串联变压器的次级端,针对此RLC支路,提出两种限流模式。(1)放电模式:电阻R与电容C被并联的功率电子开关(IGBT)旁路,而电感L仍与变压器次级端相联,从而构成直流电抗器。(2)充电模式:若串联电抗器阻抗不足以限制故障电流,可以通过选择恰当的并联IGBT开关持续时间(on-off duration),将高阻抗的串联电阻R和电容C插入电路,从而限制故障电流。 结论:通过控制直流电抗器电流幅度,可以降低故障电流并将公共耦合点(PCC)的电位限制于合理水平。此外,在本文所述的新型SSFCL中,与IGBT并联的RC支路可作为缓冲电路用于降低开关状态下IGBT的瞬态恢复电压(TRV)。因此,SSFCL可以提升电能质量。本文还给出了在已有的原型系统上的实验测量结果以支持理论和仿真研究。所述的SSFCL可以无延迟地限制故障电流并有效平滑故障电流波形。 关键词组: Darkslateblue:Affiliate; Royal Blue:Author; Turquoise:Article
Reference[1]Abramovitz, A., Smedley, K.M., 2012. Survey of solid-state fault current limiters. IEEE Trans. Power Electron., 27(6):2770-2782. ![]() [2]Amanulla, B., Chakrabarti, S., Singh, S.N., 2012. Reconfiguration of power distribution systems considering reliability and power loss. IEEE Trans. Power Deliv., 27(2):918-926. ![]() [3]Cheng, S., Chen, M.Y., Wai, R.J., et al., 2014. Optimal placement of distributed generation units in distribution systems via an enhanced multi-objective particle swarm optimization algorithm. J. Zhejiang Univ.-Sci. C (Comput. & Electron.), 15(4):300-311. ![]() [4]Cvoric, D., de Haan, S.W.H., Ferreira, J.A., 2008. Comparison of the four configurations of the inductive fault current limiter. IEEE Power Electronics Specialists Conf., p.3967-3973. ![]() [5]Du, H.I., Kim, Y.J., Lee, D.H., et al., 2011. Effect of the resistance of two different coated conductors on the current-limiting performance of flux-lock type superconducting fault current limiters. IEEE Trans. Appl. Supercond., 21(3):1254-1257. ![]() [6]Fani, B., Hamedani Golshan, M.E., Askarian Abyaneh, H., 2011. Waveform feature monitoring scheme for transformer differential protection. J. Zhejiang Univ.-Sci. C (Comput. & Electron.), 12(2):116-123. ![]() [7]Firouzi, M., Gharehpetian, G.B., Pishvaei, M., 2013. A dual-functional bridge type FCL to restore PCC voltage. Int. J. Electr. Power Energy Syst., 46:49-55. ![]() [8]Ghanbari, T., Farjah, E., 2013. Unidirectional fault current limiter: an efficient interface between the microgrid and main network. IEEE Trans. Power Syst., 28(2):1591-1598. ![]() [9]Globalspec, 2015. The Engineering Search Engine. Globalspec, Inc., USA. Available from http://www.globalspec.com ![]() [10]Hagh, M.T., Abapour, M., 2007. DC reactor type transformer inrush current limiter. IET Electr. Power Appl., 1(5):808-814. ![]() [11]Hagh, M.T., Abapour, M., 2009a. Non-superconducting fault current limiters. Eur. Trans. Electr. Power, 19(5):669-682. ![]() [12]Hagh, M.T., Abapour, M., 2009b. Nonsuperconducting fault current limiter with controlling the magnitudes of fault currents. IEEE Trans. Power Electron., 24(3):613-619. ![]() [13]Hanif, A., Choudhry, M.A., 2009. Dynamic voltage regulation and power export in a distribution system using distributed generation. J. Zhejiang Univ.-Sci. A, 10(10):1523-1531. ![]() [14]Iwahara, M., Mukhopadhyay, S.C., Yamada, S., et al., 1999. Development of passive fault current limiter in parallel biasing mode. IEEE Trans. Magn., 35(5):3523-3525. ![]() [15]Jafari, M., Naderi, S.B., Hagh, M.T., et al., 2011. Voltage sag compensation of point of common coupling (PCC) using fault current limiter. IEEE Trans. Power Deliv., 26(4):2638-2646. ![]() [16]Jang, J.Y., Park, D.K., Yang, S.E., et al., 2010. A study on the non-inductive coils for hybrid fault current limiter using experiment and numerical analysis. IEEE Trans. Appl. Supercond., 20(3):1151-1154. ![]() [17]Liu, J.M., Fan, T.R., Tong, K.Z., 2007. Research of network technology for intelligent circuit breaker controller. J. Zhejiang Univ.-Sci. A, 8(3):464-468. ![]() [18]Madani, S.M., Rostami, M., Gharehpetian, G.B., et al., 2013. Improved bridge type inrush current limiter for primary grounded transformers. Electr. Power Syst. Res., 95:1-8. ![]() [19]McAullife, J., Amin, D., Peacock, I., et al., 2001. Optimizing capital costs in power-distribution upgrades. IEEE Ind. Appl. Mag., 7(5):41-51. ![]() [20]Na, J.B., Kim, Y.J., Jang, J.Y., et al., 2012. Design and tests of prototype hybrid superconducting fault current limiter with fast switch. IEEE Trans. Appl. Supercond., 22(3):5602604. ![]() [21]Radmanesh, H., Fathi, S.H., Gharehpetian, G.B., 2015a. Novel high performance DC reactor type fault current limiter. Electr. Power Syst. Res., 122:198-207. ![]() [22]Radmanesh, H., Fathi, S.H., Gharehpetian, G.B., 2015b. Series transformer based solid state fault current limiter. IEEE Trans. Smart Grid, 6(4):1983-1991. ![]() [23]Tsuda, M., Mitani, Y., Tsuji, K., et al., 2001. Application of resistor based superconducting fault current limiter to enhancement of power system transient stability. IEEE Trans. Appl. Supercond., 11(1):2122-2125. ![]() [24]Vintan, M., 2008. Evaluating transmission towers potentials during ground faults. J. Zhejiang Univ.-Sci. A, 9(2):182-189. ![]() [25]Wu, Z.L., Chen, P.P., Tan, L.Y., et al., 2001. Short circuit current limiter in AC network. J. Zhejiang Univ.-Sci., 2(1):41-45. ![]() [26]Yamaguchi, H., Kataoka, T., 2008. Current limiting characteristics of transformer type superconducting fault current limiter with shunt impedance and inductive load. IEEE Trans. Appl. Supercond., 18(2):668-671. ![]() [27]Ye, L., Lin, L.Z., Juengst, K.P., 2002. Application studies of superconducting fault current limiters in electric power systems. IEEE Trans. Appl. Supercond., 12(1):900-903. ![]() [28]Zhao, C., Lu, J.Z., Fang, Z., et al., 2010. Study of a novel fault current limiter on the basis of high speed switch and triggered vacuum switch. 5th Int. Conf. on Critical Infrastructure, p.1-5. ![]() Journal of Zhejiang University-SCIENCE, 38 Zheda Road, Hangzhou
310027, China
Tel: +86-571-87952783; E-mail: cjzhang@zju.edu.cn Copyright © 2000 - 2025 Journal of Zhejiang University-SCIENCE |
Open peer comments: Debate/Discuss/Question/Opinion
<1>
Hamid@Radmanesh<hamid.nsa@gmail.com>
2015-05-27 18:38:38
Dear Dr.Editor,
I am Dr.Hamid Radmanesh the second author of this paper. Would you please replace my second affiliation with this affiliation "Aeronautical University of Science and Technology, Tehran, Iran".
I am waiting for your response.
Best Regards,
Radmanesh, PhD